Rating | 105 deg C, 600 Vac, Cable flame. |
|
Conductor | 32 AWG - 16 AWG, solid or stranded. |
|
Insulation | Extruded XLPE, 30 mils minimum average thickness, 27 mils minimum thickness at any point. |
|
Assembly | Two or more twisted singles or groups of twisted singles twisted together may be laid parallel to form flat, oval, or round cables. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. |
|
Covering | Optional. Extruded PVC, 5 mils minimum thickness at any point. |
|
Shield | Optional. May be over one or more of the insulated conductors or applied over the assembly. |
|
Jacket | Extruded PVC. |
| dia of cable under jacket |
| 0.424 inches or less | 30 mils minimum average thickness | 27 mils minimum thickness at any point |
| 0.425-0.700 dia | 60 avg | 48 min |
| 0.701-1.500 dia | 80 avg | 64 min |
| 1.501-2.500 dia | 110 avg | 88 min |
| 2.501 dia and larger | 140 avg | 112 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring or external interconnection in electronic equipment where each end is terminated in connectors. |
|