APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4392 Issued:1989-04-20
Revised:2012-01-11
Style 4392 Multiple-conductor cable using non-integral jacket

Rating90 deg C, 300 Vac, Cable flame.
Conductor18-10 AWG or smaller stranded, tinned or bare copper.
InsulationLabeled or complying with manufacturer's AWM procedure.
AssemblyTwo or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
ShieldOptional.
CoveringA 6 mil or heavier PVC covering may be extruded over the conductor assembly.
BraidOptional.
JacketNR - NEOPRENE, If the diameter of cable under the jacket is 0.700 or less, 45 mils min average, 36 mils minimum at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnection or internal wiring of appliances or electronic equipment.

UL and the UL Logo are trademarks of UL LLC © 2024