Rating | 75 deg C, 300 Vac, Cable Flame. |
|
Insulation | Labeled or complying with Manufacturer's AWM Procedure. |
|
Assembly | Two or more singles, twisted pairs of groups of twisted singles twisted together. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. May be straight or coiled in the form of a helix. |
|
Jacket | Extruded Neoprene - |
| diameter of cable under jacket in inches | mils minimum average | mils minimum at any point |
| 0.700 or less | 30 | 24 |
| 0.701-1.000 | 45 | 36 |
| 1.001-1.500 | 60 | 48 |
| 1.501-2.500 | 80 | 64 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External interconnection or internal wiring of appliances or electronic equipment. |
|