APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4402 Issued:1991-02-25
Revised:2012-04-02
Style 4402 Multiple-Conductor Cable Using Extruded Non-Integral Jacket

Rating90 deg C, 600 Vac, FT2 flame, Oil Resistant 60 deg C.
Conductor18 AWG - 10 AWG smaller stranded, tinned or bare.
InsulationExtruded CP or CPE or EP or NBR/PVC or NR - NEOPRENE or SRB/NR or XL, 30 mils minimum average thickness, 27 mils minimum thickness at any point.
AssemblyTwo to four conductors, same as type SO Cord.
JacketSee Facing Page for Compound Identification
Diameter of core assembly under jacket (inches)Minimum average thickness (mils)Minimum thickness at any point (mils)
0-0.5004536
0.501-0.7506048
0.751-1.0008064
1.001-1.50011088
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseSpecial use power supply cords used in appliances such as Commercial Cooking Appliances.