Rating | 125 deg C, 600 Vac. |
|
Conductor | 18 AWG - 4/0AWG, Stranded Round. |
|
Insulation | Extruded XLPE |
| AWG Conductor Size | mils minimum average | mils minimum at any point |
| 18-10 | 30 | 27 |
| 9-2 | 45 | 40 |
| 1-4/0 | 55 | 50 |
| or Labeled or complying with manufacturer's AWM procedure. |
|
Assembly | Two or more conductors, fillers and/or barrier tapes optional. |
|
Shield | Optional - Braid and/or Metallic Tape. |
|
Jacket | Extruded XL - See facing page for compound |
| dia of cable under jacket in inches | mils minimum average | mils minimum at any point |
| 0-0.500 | 30 | 24 |
| 0.501-0.750 | 45 | 36 |
| 0.751-1.500 | 60 | 48 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Special use power supply cords used in high temperature equipment. |
|