APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4423 Issued:1993-04-09
Revised:2019-11-07
Style 4423 Jacketed Cord

Rating90 deg C, 600 Vac, Horizontal flame, Moisture Resistant 60 or 75 deg C (optional).
InsulationCP or CPE or EP or NBR/PVC or NR - NEOPRENE or SRB/NR or XL
.75 -1.0 mm conductor size30 mils min average27 mils minimum at any point
1.01-6.0 mm45 avg40 min
6.01-25.0 mm60 avg54 min
AssemblySame as Types S, SO, SW-A or SOW-A.
JacketCP or EPDM or NBR/PVC or NR - NEOPRENE or SRB/NR
dia of cable under jacket
0.500 inches or less80 mils min average64 mils minimum at any point
0.501-0.750 dia95 avg76 min
0.751-1.000 dia110 avg88 min
1.001-1.500 dia125 avg100 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnection of appliances and electronic equipment outdoor and in wet locations (60 degrees or 75 degrees).