APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4426 Issued:1993-06-11
Revised:2019-10-11
Style 4426 Multiple-conductor cable using non-integral jacket

Rating150 deg C, 600 Vac, Horizontal flame.
Conductor30 AWG - 4 AWG solid or stranded round, tinned or bare copper.
InsulationXLPE.
conductor sizemin averageminimum at any point
30-9 AWG30 mils27 mils
8-4 AWG45 avg40 min
or labeled or complying with manufacturer's AWM procedure.
AssemblyTwo to six conductors, fillers and/or barrier tapes optional.
JacketXLPE
dia of cable under jacketmin averageminimum at any point
0-0.500 inches30 mils24 mils
0.501-0.750 dia45 mils36 mils
0.751-1.000 dia60 mils48 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseSpecial use power supply cords or external interconnection used in high temperature equipment such as appliances, electronics and lighting equipment where the acceptability of the combination will be determined by Underwriters Laboratories.

UL and the UL Logo are trademarks of UL LLC © 2024