APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4435 Issued:1995-06-02
Revised:2019-11-07
Style 4435 Multiple-Conductor Cable using Non-Integral Jacket

Rating90 deg C, 300 Vac, Cable flame.
InsulationLabeled or complying with manufacturer's AWM procedure.
AssemblyTwo or more individually insulated conductors or groups of insulated conductors cabled together. All conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or groups is not specified. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or a thermoplastic-tape wrap. Such a barrier layer would serve to protect the cable during further processing, and would be applied immediately over the twisted assembly of individual conductors or groups of conductors.
ShieldOptional.
CoveringOptional - An IRPE covering may be extruded over the conductor assembly, having minimum thickness of 10 mils.
BraidOptional.
JacketExtruded XLPE - See facing page for compound identification
dia of cable under jacket
0.700 inches or less30 mils min average24 mils minimum at any point
0.701 to 1.000 dia45 avg36 min
1.001 to 1.500 dia60 avg48 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnection of electronic equipment.