|
Rating | 90 deg C, 600 Vac, Cable flame. |
|
Conductor | 18 AWG - 2 AWG, stranded. |
|
Insulation | Labeled or complying with manufacturer's AWM procedure. |
|
Assembly | Two or more individually insulated conductors or groups of insulated conductors laid parallel or cabled together to form a flat, oval or round cable. Conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or groups is not specified. The use of a barrier layer and/or fillers is optional. Fillers, tape wrap, braid or extruded covering may be used. |
|
Jacket | Extruded NBR/PVC |
| dia of cable under jacket |
| 0.425 inches or less | 45 mils min average | 36 mils minimum at any point |
| 0.426-0.700 dia | 60 avg | 48 min |
| 0.701-1.500 dia | 80 avg | 64. min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Interconnection of Electronic Equipment. |
|