Rating | 90 deg C, 600 Vac, Horizontal flame, Cable flame. |
|
Conductor | 18 AWG - 10 AWG solid or stranded. |
|
Insulation | EP |
| 18-16 AWG conductor size | 30 mils minimum average | 27 mils minimum at any point |
| 14-10 AWG | 45 avg | 40 min |
|
Assembly | Two or more individually insulated conductors or groups of insulated conductors cabled together. All conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or group is not specified. A barrier layer, if employed, may be a fibrous wrap serving, or braid, paper; nylon; oriented polyethylene terephthalate; or a thermoplastic-tape wrap. Such a barrier layer would serve to protect the cable during further processing, and would be applied immediately over the twisted assembly of individual conductors or groups of conductors. |
|
Covering | Covering - Nylon, - 3 mil minimum at any point. |
|
Jacket | NBR/PVC |
| dia of the cable under jacket |
| 0.700 inches or less | 110 mils minimum average | 88 mils minimum at any point |
| 0.701-1.000 dia | 130 avg | 104 min |
| 1.001-1.500 dia | 150 avg | 120 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring or external interconnection of electric equipment of appliances. |
|