Rating | 150, 200 deg C, 1000 Vac, Cable flame. |
|
Conductor | 21 AWG - 250 kcmil solid or stranded round. |
|
Insulation | Extruded SR - SILICONE |
| 0.5-1.5 sq mm conductor size | 38 mils min average | 34 mils minimum at any point |
| 2.5 sq mm | 42 avg | 37 min |
| 4-6 sq mm | 47 avg | 37 min |
| 10-16 sq mm | 57 avg | 51 min |
| 25-35 sq mm | 66 avg | 61 min |
| 50-70 sq mm | 75 avg | 70 min |
| 95-120 sq mm | 85 avg | 80 min |
|
Assembly | May be applied in two layers with and intermediate glass braid (optional). Assembly - Two conductors laid parallel with interconnecting web. Minimum thickness at any point shall be the same as above after separation. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring. |
|