Rating | 150, 200 deg C, 150, 300, 600, 1000 Vac, Construction A Horizontal flame, Construction B Cable Flame. |
|
Conductor | 50 AWG - 2000 kcmil, solid or stranded. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more conductors, twisted together. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | Optional. |
|
Jacket | Extruded Silicone |
| dia of cable under jacket | Construction |
| 0.700 inches or less | construction A | 30 mils min average | 24 mils minimum at any point |
| 0.700 inches or less | construction B | 45 avg | 36 min |
| 0.701-1.000 dia | construction A | 45 avg | 36 min |
| 0.701-1.000 dia | Construction B | 60 avg | 48 min |
| 1.001-1.500 dia | construction A | 60 avg | 48 min |
| 1.001-1.500 dia | construction B | 80 avg | 64 min |
| 1.501-2.500 dia | construction A | 60 avg | 48 min |
| 1.501-2.500 dia | construction B | 95 avg | 76 min |
|
Shield | Optional, Metal Wire Braid. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Construction A Internal wiring. Construction B External wiring. |
|