Rating | 90 deg C, 150 Vac, Cable flame, 60 deg C Oil. |
|
Insulation | Labeled and/or complying with manufacturer AWM Procedure. |
|
Assembly | Two or more individually insulated conductors or groups of insulated conductors cabled together. The length of lay of the twisted conductors or groups is not specified. |
|
Shield | Optional. |
|
Jacket | Extruded Neoprene. |
| Diameter of the cable under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.425 inches or less | 30 mils | 24 mils |
| 0.426-0.700 inch | 45 mils | 46 mils |
| 0.701-1.000 inch | 60 mils | 48 mils |
| 1.001-1.500 inch | 80 mils | 62 mils |
| 1.501-2.500 inch | 110 mils | 88 mils |
| 2.501 inch and larger | 140 mils | 112 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring or External Interconnection of Electronic Equipment. |
|