APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4507 Issued:2002-07-12
Revised:2016-07-29
Style 4507 Multiple-conductor cable using non-integral jacket.

Rating90 deg C, 600 Vac, VW-1 flame, Cable Flame, Oil Resistant 60 deg C.
Conductor18 AWG - 2000 kcmil, solid or stranded. Same as Type SO Cord except 40 AWG - 37 AWG strands may be used. Aramid fiber strength member may be employed as a central member in stranded conductors.
InsulationExtruded EP, 30 mils minimum average thickness, 27 mils minimum thickness at any point.
AssemblyTwo or more conductors.
ShieldOptional.
JacketExtruded neoprene, 60 mils minimum average thickness, 48 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal or External Wiring of Electronic Equipment where exposed to oil at a temperature not exceeding 60 deg C and where the final acceptability is to be determined by UL LLC.