Rating | 90 deg C, 600 Vac, VW-1 flame, Cable Flame, Oil Resistant 60 deg C. |
|
Conductor | 18 AWG - 2000 kcmil, solid or stranded. Same as Type SO Cord except 40 AWG - 37 AWG strands may be used. Aramid fiber strength member may be employed as a central member in stranded conductors. |
|
Insulation | Extruded EP, 30 mils minimum average thickness, 27 mils minimum thickness at any point. |
|
Assembly | Two or more conductors. |
|
Shield | Optional. |
|
Jacket | Extruded neoprene, 60 mils minimum average thickness, 48 mils minimum thickness at any point. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal or External Wiring of Electronic Equipment where exposed to oil at a temperature not exceeding 60 deg C and where the final acceptability is to be determined by UL LLC. |
|