APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4511 Issued:2002-09-30
Revised:2013-02-21
Style 4511 Multiple-conductor cable using non-integral jacket

Rating200 deg C, 600 Vac, Horizontal flame.
Insulated ConductorLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more conductors. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly.
CoveringOptional, Extruded SR, 6 mils minimum thickness at any point.
ShieldOptional.
JacketExtruded SR.
Diameter of cable under jacketMinimum average thicknessMinimum thickness at any point
0-0.700 inches / 0-17.78 mm34 mils / 0.86 mm32 mils / 0.81 mm
0.701-1.000 inch / 7.79-25.40 mm45 mils / 1.14 mm36 mils / 0.91 mm
1.001-1.500 inch / 25.41-38.10 mm60 mils / 1.52 mm48 mils / 1.22 mm
1.501-2.500 inch / 38.11-63.50 mm80 mils / 2.03 mm64 mils / 1.63 mm
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnection not subject to mechanical abuse and where the acceptability of the combination is to be determined by UL.