APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4535 Issued:2005-06-29
Revised:2012-11-26
Style 4535 Multiple-conductor cable using non-integral jacket

Rating150 deg C, 600 Vac, Horizontal flame.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more conductors. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly.
CoveringOptional. Extruded SR, 6 mils minimum thickness at any point.
ShieldOptional.
JacketExtruded SR.
Diameter of assembly under jacketMinimum average thicknessMinimum thickness at any point
0-0.700 in.30 mils24 mils
0.701-1.000 in.45 mils36 mils
1.001-1.500 in.60 mils48 mils
1.501-2.500 in.80 mils64 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnection not subject to mechanical abuse.

UL and the UL Logo are trademarks of UL LLC © 2024