Rating | 150 deg C,1000 Vac Cable flame. |
|
Conductor | 50 AWG - 2000 kcmil, solid or stranded. |
|
Insulation | Extruded XLPO |
| Conductor size | Minimum average thickness | Minimum thickness at any point |
| 50-10 AWG | 30 mils | 27 mils |
| 9-8 AWG | 45 mils | 40 mils |
| 7-2 AWG | 60 mils | 54 mils |
| 1-4/0 AWG | 80 mils | 72 mils |
| 250-500 kcmil | 95 mils | 86 mils |
| 501-1000 kcmil | 110 mils | 99 mils |
| 1001-2000 kcmil | 125 mils | 112 mils |
|
Assembly | Two or more singles, twisted pairs or groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval, or round cables. May use same or mixed AWG size. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly |
|
Covering | Optional |
|
Shield | Optional |
|
Jacket | Extruded XLPO |
| dia. in inches |
| 0-1.000 dia | 45 mils min average | 36 mils minimum at any point |
| 1.001-1.500 dia | 60 avg | 48 min |
| 1.501-2.500 dia | 80 avg | 64 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Wiring. |
|