APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4598 Issued:2014-05-09
Revised:2014-05-12
Style 4598 Multiple-conductor cable using non-integral jacket.

Rating150 deg C, 600 Vac, Cable flame.
Insulated ConductorLabeled or complying with manufacture's AWM procedures.
AssemblyConsists of two or more conductors, twisted pairs, or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. A barrier layer and/or fillers are optional.
CoveringOptional.
ShieldOptional.
JacketExtruded SR.
Diameter of core assembly under jacket (Inches)Minimum average thickness (Mils)Minimum thickness at any point (Mils)
0.700 or less3024
0.701 - 1.0004536
1.001 - 1.5006048
1.501 - 2.5008064
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024