Rating | 105 deg C, 15000 Vac, Horizontal flame. |
|
Conductor | 26 AWG - 14 AWG, solid or stranded. |
|
Insulation | Extruded XLPE, 94 mils minimum average thickness, 85 mils minimum thickness at any point. |
|
Assembly | Two or more conductors, twisted pairs, or groups of twisted conductors. The conductors may be laid parallel or twisted together to form a flat, oval, or round cable construction. Barrier layer, tapes and/or fillers optional. May use same or mixed AWG sizes. Manufacturer shall maintain a complete description of each assembly. |
|
Inner Jacket | Extruded PVC, 39 mils minimum average thickness, 31 mils minimum thickness at any point, extruded over each insulated conductor. |
|
Shield | Optional. |
|
Covering | Optional. |
|
Jacket | Extruded PVC. |
| Diameter of core assembly under jacket (inches) | Minimum average thickness (mils) | Minimum thickness at any point (mils) |
| 1.500 or less | 70 | 56 |
| 1.501-2.500 | 80 | 64 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring. |
|