Rating | 80 deg C, 300 Vac, Cable Flame |
|
Conductor | 22 AWG - 12 AWG, Stranded Metal Coated Copper |
|
Insulation | Extruded PP - 10 mils minimum average thickness, 9 mils minimum at any point or Extruded PVC - 32 mils minimum average thickness, 29 mils minimum average thickness. |
|
Assembly | One or more pairs of PP insulation with barrier, metal coated drain wire, and AL/Polyester Foil Shield. One or more PVC insulated conductors. PP and or Kevlar Fillers and PP Binder. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or a thermoplastic-tape wrap. Such a barrier layer would serve to protect the cable during further processing, and would be applied immediately over the twisted assembly of individual conductors or groups of conductors. May use same or mixed AWG sizes. Manufacturer shall maintain a complete description of each assembly. |
|
Jacket | Extruded CPE |
| diameter of round assembly under jacket in inches | average thickness in mils | minimum thickness in mils |
| 0-1.500 | 60 | 48 |
| 1.5001-2.500 | 80 | 64 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Wiring. |
|