APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4660 Issued:2024-02-27
Revised:2024-02-28
Style 4660 Multiple-Conductor Cable Using Extruded Non-Integral Jacket

Rating150 deg C, 300 Vac, Cable Flame.
Conductor40 AWG - 14 AWG, solid or stranded.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Barrier layer and/or fillers optional. Covering or metal shield optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
CoveringOptional.
ShieldOptional.
JacketExtruded SR - May be provided in one or more non-separable layers with below total thickness.
Diameter of Round Assembly under jacket (inches)Minimum average thickness (mils)Minimum thickness at any point (mils)
0.700 or less3024
0.701-1.0004536
1.001-1.5006054
1.501-2.5008064
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring or Internal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2025