APPLIANCE WIRING MATERIAL
Subj.758 Section 5 Page 5048 Issued:1987-07-10
Revised:2012-04-13
Style 5048 Single conductor with other-than-extruded insulation.

Rating105 deg C, 600 Vac.
Conductor22 AWG - 1 AWG, consisting 30 - 38 AWG strands, Same as Type ST cords except that rope lay stranding may be used in all conductor sizes. The length of lay of the individual strands comprising each concentric stranded member in a rope-lay conductor shall neither be less than 8 nor more than 16 times the overall diameter of the member. The length of lay of the individual strands comprising each bunch stranded member in a rope-lay conductor shall not be more than 30 times the overall diameter of the member.
InsulationPET tape, 0.5 mil minimum thickness, applied with half lap between inner and outer closely woven PET fiber braids.
AssemblyThe maximum length of lay of members shall be as indicated below.
Conductor sizemaximum length of lay of members
22-19 AWG1.0 in
18-11 AWG2.0 in
10-9 AWG2.5 in
8-7 AWG2.75 in
6-5 AWG3.5 in
4-3 AWG4.5 in
2-1 AWG5.5 in
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseWire within hermetic motors where the acceptability of the combination is to be determined by UL LLC.