| Rating | 200 deg C, 600 Vac. |
|
| Conductor | 22 AWG - 4/0 AWG, solid or stranded. |
|
| Insulation | Aramid tape, 7.5 mils minimum average thickness. |
|
| Assembly | Aramid tape, 2.5 mils minimum average thickness, 0.250 inch minimum width is spirally wrapped with a min overlap of 80 mils. 3 separate layers applied one over the other, covered with a treated or untreated glass or aramide braid. |
|
| Covering | Modified epoxy varnish treated glass or untreated Aramid braid; for No. 22-10 AWG. For No. 8-4/0 AWG, 24 carriers. |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | Lead wire within hermetic, enclosed, or high-temperature motors where the acceptability of the combination is to be determined by Underwriters Laboratories Inc. |
|