Rating | 200 deg C, 600 Vac. |
|
Conductor | 8 AWG - 4/0 AWG, Solid or Stranded Round. |
|
Insulation | Non-Extruded Aramid, 2.5 mil minimum thickness, 0.25 in. wide minimum. |
|
Assembly | The Aramid tape is spirally wrapped with a 45% min. overlap. Four separate layers applied one over the other. |
|
Covering | Modified epoxy varnish treated glass or untreated aramid braid: for 8-4/0 AWG, 24 carriers and as noted following. |
| AWG Size | 8 | 6 | 4 | 3 | 2 | 1 | 1/0 | 2/0 | 3/0 | 4/0 |
| Number of ends | 3 | 4 | 4 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
| Picks per inch min. | 12 | 10.5 | 12 | 10.5 | 10.5 | 10.5 | 12 | 12 | 12 | 13 |
| Optional - 2 Non-Extruded Glass Braids of 1-4/0 AWG. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Lead wire within hermetic, enclosed, or high-temperature motors where the acceptability of the combination is to be determined by Underwriters Laboratories Inc. |
|