| Rating | 250 deg C, 600 Vac, Horizontal Flame. |
|
| Conductor | 26 AWG - 6 AWG, solid or stranded. |
|
| Insulation | Extruded PTFE. |
| Conductor size | Minimum average thickness |
| 26-10 AWG | 10 mils |
| 9-6 AWG | 16 mils |
|
| Covering | Treated glass braid. |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|