APPLIANCE WIRING MATERIAL
Subj.758 Section 5 Page 5331 Issued:1993-04-13
Revised:2012-11-21
Style 5331 Single conductor with other-than-extruded insulation and covering

Rating250 deg C, 300 Vac, Horizontal flame.
Conductor24 AWG - 8 AWG, solid or stranded.
InsulationPTFE tape, 10 mils minimum thickness at any point, with two layers of fiberglass tape, 10 mils minimum average thickness, 8 mils minimum thickness at any point.
CoveringTreated Glass Braid.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.