Rating | 350 deg C, 300 Vac, Horizontal flame. |
|
Conductor | 24 AWG - 4 AWG solid or stranded round, nickel alloy, or 27% minimum nickel coated copper |
|
Insulation | MICA or PTFE, TFE |
| Mica glass | 24-12 AWG conductor size | 17 mils min average |
| Mica glass | 11-4 AWG | 20 avg |
| Glass braid treated with silicone varnish or TFE finish | 24-12 AWG | 5 avg |
| Glass braid treated with silicone varnish or TFE finish | 11-4 AWG | 10 avg |
|
Shield | Optional. Applied as a braid over the treated glass braid. |
|
Braid | Optional. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring where not subjected to flexing or mechanical abuse. |
|