APPLIANCE WIRING MATERIAL
Subj.758 Section 5 Page 5400 Issued:2002-12-19
Revised:2023-12-01
Style 5400 Single Conductor with Other-Than-Extruded Insulation

Rating550 deg C, 600 Vac, Horizontal flame.
Conductor24 AWG - 550 kcmil solid or stranded round. Nickel-chromium alloy allowed.
InsulationComposite consisting of MICA with treated fiberglass braid.
AWG Conductor SizeMinimum average thickness (mils)Minimum thickness at any point (mils)
24-123229
11-44541
3-4/05550
250-550 kcmil6054
ShieldOptional. Stainless steel, alloy 304, applied as a braid over treated glass braid.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024