APPLIANCE WIRING MATERIAL
Subj.758 Section 5 Page 5534 Issued:2013-08-27
Revised:New
Style 5534 Single-conductor cable employing a non-extruded covering as the outermost layer.

Rating200 deg C, 600 Vac, Horizontal flame.
Conductor50 AWG - 10 AWG, solid or stranded.
InsulationNon-extruded PTFE tape wrapped and sintered, 7 mils minimum average thickness, 6 mils minimum thickness at any point.
Inner CoveringOptional.
Outer CoveringGlass fiber braid treated with silicone varnish coating, 5 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring where not subjected to movement or mechanical abuse.