APPLIANCE WIRING MATERIAL
Subj.758 Section 5 Page 5555 Issued:2015-09-25
Revised:New
Style 5555 Multiple conductor cable with optical fiber members using non-integral jacket.

Rating80 deg C, 300 Vac, Voltage not applicable to Fiber Optic, Cable flame.
Insulated ConductorLabeled or complying with Manufacturer's AWM Procedure.
Fiber OpticCoated glass or plastic fiber with optional buffer layer and optional covering.
AssemblyOne or more optical fiber members are cabled together as round or flat assembly with two or more insulated conductors within overall PVC jacket. Fillers and/or binder tapes may be employed. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. Jackets may be co-extruded in such a fashion to form a flat cable and may have an interconnecting web.
ShieldOptional.
JacketExtruded PVC.
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024