APPLIANCE WIRING MATERIAL
Subj.758 Section 5 Page 5562 Issued:2016-11-30
Revised:2020-05-12
Style 5562 Single conductor with other-than-extruded insulation

Rating550 deg C,600 Vac, Horizontal flame.
Conductor24 AWG - 550 kcmil solid or stranded round. Nickel-chromium alloy allowed.
InsulationComposite construction consisting of mica insulation covered by a treated fiberglass braid
AWG Conductor SizeMinimum average thickness (mils)Minimum thickness at any point (mils)
24-123229
11-44541
3-4/05550
250-550 kcmil6054
ShieldOptional. Stainless steel, alloy 304, applied as a braid over treated glass braid.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring where not subject to movement after installation.

UL and the UL Logo are trademarks of UL LLC © 2024