APPLIANCE WIRING MATERIAL
Subj.758 Section 5 Page 5571 Issued:2017-10-05
Revised:New
Style 5571 Single conductor cable with non-extruded insulation and non-extrued covering

Rating200 deg C, 1000 Vac, Horizontal flame.
Conductor22 AWG - 4/0 AWG, stranded.
InsulationNon extruded insulation consisting of 3 non-extruded layers. Inner layer is Polyimide tape with minimum average thickness 1 mil; middle layer is Mica tape with minimum average thickness 8 mils and outer layer is Polyimide tape with minimum average thickness 1.2 mils.
AssemblySingle conductor with multi-layered insulation and 2 overall fiberglass braids.
CoveringTwo non-extruded fiberglass braids with varnish shall be provided over the insulation. Each braid shall have a minimum thickness of 12 mils.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024