APPLIANCE WIRING MATERIAL
Subj.758 Section 5 Page 5588 Issued:2021-11-08
Revised:2021-12-17
Style 5588 Multiple conductor with other-than-extruded Covering

Rating150 deg C, 600 Vac, Horizontal flame.
InsulationLabeled or complying with Manufacture's AWM Procedure.
AssemblyTwo or more insulated conductors, each with a fiberglass braid (inner covering), cabled together into a round cable. There shall be an inner shield, binder tape(s), optional fillers, and an outer non-extruded fiberglass braid and an optional overall metal braid, as described below.
Inner CoveringNon-extruded fiberglass braid with 6 mils minimum average thickness, 5 mils minimum thickness at any point, provided over each insulated conductor.
Inner ShieldMetallic braid or tape provided over the cable core.
BinderOne or more non extruded PTFE tapes provided over the inner shield.
Outer CoveringNon-extruded fiberglass braid with 18 mils minimum average thickness and 17 mils minimum thickness at any point, provided over the Binder Tape.
Outer BraidOptional - stainless steel braid.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring of Electronic Equipment or Appliances for Equipment Interconnection