UL
iQ
for Surge Protective Devices
Surge Protective Devices
E320116
Guide Information
LITTELFUSE INC
8755 W HIGGINS RD STE 500, CHICAGO IL 60631
Cat No(s): V385LA40CP (e)
C-III Series
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)
Notes
5
385
AC
1
n/a
-40
105
Ld-Ld
-
2030
385
620
5
n/a
1
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08 and CSA C22.2 No. 269.5-17, 2017-09
(e) -
All part numbers may be followed by additional suffixes except X3683 and X3588; and LA may be replaced by LC, LS, LT or LU.
Note -
Each model may be suffixed by X, where X may be blank, A thru Z or from 0 thru 9.
Note 1 -
Suitable for Factory wiring only.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2012-02-24
© 2024 UL Solutions
Last Revised:
2021-07-20