UL
iQ
for Surge Protective Devices
Surge Protective Devices
E316410
Guide Information
EATON
1000 CHERRINGTON PKWY, MOON TOWNSHIP PA 15108-4312
Cat No(s): SPD200480Y@%(c)
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)
Notes
2CA
480/277
AC
3Y
n/a
0
40
L-L
2000
-
640
-
20
200
1
L-N
1500
-
320
-
L-G
1500
-
320
-
N-G
1200
-
320
-
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08
% -
Follwed by D, E, F, G or H.
(c) -
Models Complementary Recognized as (FOKY2), E316410.
@ -
Where x may be replaced by 2 or 3.
Note 1 -
Suitable for Factory wiring only.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.