UL
iQ
for Surge Protective Devices
Surge Protective Devices
E320116
Guide Information
LITTELFUSE INC
8755 W HIGGINS RD STE 500, CHICAGO IL 60631
Cat No(s): V10H320(P)
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)
Notes
5
320
AC
1
n/a
-40
125
Ld-Ld
-
1300
320
510
2
n/a
1,5a
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15 and CSA C22.2 No. 269.5-17, 2017-09
(P) -
May be followed by P or other suffixes, may be followed by L1, L2, L3, L4 or L5, may be followed by 1, 2, 3, 4, or 5, may be followed by B, T or A, may be followed by 5, 7 or 1, may be followed by additional suffixes.
Note -
Each model may be suffixed by X, where X may be blank, A thru Z or from 0 thru 9.
Note 1 -
Suitable for Factory wiring only.
Note 5a -
Body of discrete component metal-oxide varistors (MOVs) flammability: Min. V-0 or VTM-0.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2015-03-31
© 2024 UL Solutions
Last Revised:
2023-10-05