UL
iQ
for Surge Protective Devices
Surge Protective Devices
E328921
Guide Information
DIVERSIFIED TECHNOLOGY GROUP INC, DBA DITEK
1720 STARKEY RD, LARGO FL 33771-3120
Model(s): D100-4803D
Permanently Connected, D100 Series
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1
380
AC
3D
n/a
-35
60
L-L
4000
960
20
100
L-G
1800
480
1
400
AC
3D
n/a
-35
60
L-L
4000
960
20
100
L-G
1800
480
1
415
AC
3D
n/a
-35
60
L-L
4000
960
20
100
L-G
1800
480
1
440
AC
3D
n/a
-35
60
L-L
4000
960
20
100
L-G
1800
480
1
480
AC
3D
n/a
-35
60
L-L
4000
960
20
100
L-G
1800
480
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15 and CSA C22.2 No. 269.1-17, 2017-02
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2010-01-22
© 2024 UL Solutions
Last Revised:
2024-06-12