UL
iQ
for Surge Protective Devices
Surge Protective Devices
E315238
Guide Information
LEA INTERNATIONAL INC
10701 N AIRPORT RD, HAYDEN LAKE ID 83835-9742
Model(s): SP100 120/208-1
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1
208/120
AC
3Y
n/a
-35
80
L-L
1200
239
20
100
L-N
700
138
L-G
700
138
N-G
700
138
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15 and CSA C22.2 No. 269.1-17, 2017-02
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2007-12-14
© 2024 UL Solutions
Last Revised:
2023-11-14