UL
iQ
for Surge Protective Devices
Surge Protective Devices
E316468
Guide Information
RAYCAP INC
806 S Clearwater Loop, Post Falls ID 83854
Model(s): 347-3Y-M3-4-XY-D (1-port)(a), 1-51-SSY-B-H-0100-R-1XF (1-port)(a)
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
2
600/347
AC
3Y
n/a
-35
85
L-L
3000
960
20
200
L-N
3000
960
L-G
1800
480
N-G
1800
480
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08 and CSA C22.2 No. 269.2-17, 2017-02
(a) -
XX may be any alphanumeric
Note -
All models may be followed by additional suffixes.
XY -
Where XY are together X can be O, N, or P and Y can be 0, 3, 4, 5, 6, 8, 00, 03, 04, or 06
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2009-03-18
© 2024 UL Solutions
Last Revised:
2021-08-25