UL
iQ
for Surge Protective Devices
Surge Protective Devices
E320456
Guide Information
ABB Inc.
5900 Eastport Blvd, Richmond VA 23231-4459
Model(s): TPME 120Y%WMN#T1, TPR7 120Y%WMN#T1, TPHE 120Y%WMN#T1
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1
208/120
AC
3Y
n/a
0
40
L-L
1200
300
20
200
L-N
900
150
L-G
800
150
N-G
700
150
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15
# -
Where # represents 01, 04, 1D, 4D, 4F, 4S, 4X, 12F or 12S.
% -
Where % represents 06, 08, 10, 12, 15, 20, 25 or 30.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2009-10-02
© 2025 UL Solutions
Last Revised:
2023-06-27