Surge Protective DevicesE314042
Guide Information
Schneider Electric USA, Inc.
Schneider Electric, SURGE PROTECTION BUSINESS, 1751 S 4800 W, Salt Lake City UT 84104
Model(s): SDSA4040
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1480/277AC3Yn/a-3580L-L250084010200
L-N1200420
1415/240AC3Yn/a-3580L-L250084010200
L-N1200420
1400/230AC3Yn/a-3580L-L250084010200
L-N1200420
1380/220AC3Yn/a-3580L-L250084010200
L-N1200420
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08 and CSA C22.2 No. 269.1-17, 2017-02
Note - All models may be followed by additional suffixes.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.