UL
iQ
for Surge Protective Devices
Surge Protective Devices
E314042
Guide Information
Schneider Electric USA, Inc.
Schneider Electric, SURGE PROTECTION BUSINESS, 1751 S 4800 W, Salt Lake City UT 84104
Model(s): SDSA3650, SDSA3650E
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1
480/277
AC
3Y
n/a
-35
80
L-L
3000
1020
10
200
L-N
1800
510
1
600/347
AC
3Y
n/a
-35
80
L-L
3000
1020
10
200
L-N
1800
510
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08 and CSA C22.2 No. 269.1-17, 2017-02
Note -
All models may be followed by additional suffixes.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2015-05-01
© 2024 UL Solutions
Last Revised:
2023-03-29