ULiQfor Surge Protective Devices

Surge Protective DevicesE316410
Guide Information
EATON
1000 CHERRINGTON PKWY, MOON TOWNSHIP PA 15108-4312
Model(s): SP1-480D, CHSPT1-480D, PX1-NN400, SP3-480D, PX3-NN400
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1380AC3Dn/a-3550L-L200064020200
L-G2000640
1400AC3Dn/a-3550L-L200064020200
L-G2000640
1415AC3Dn/a-3550L-L200064020200
L-G2000640
1440AC3Dn/a-3550L-L200064020200
L-G2000640
1480AC3Dn/a-3550L-L200064020200
L-G2000640
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15 and CSA C22.2 No. 269.1-17, 2017-02
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2010-08-05© 2024 UL Solutions
Last Revised:2024-05-02