UL
iQ
for Surge Protective Devices
Surge Protective Devices
E319777
Guide Information
DEHN SE
Hans-Dehn-Strasse 1, Neumarkt 92318 DE
Cat No(s): 952 307
DEHNguard M
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)
Notes
4CA
690/400
AC
3Y
n/a
-40
85
L-L
-
4740
1500
n/a
10
n/a
2
L-G
-
3460
750
-
4CA
600
AC
3D
n/a
-40
85
L-L
-
4740
1500
n/a
10
n/a
2
L-G
-
3460
750
-
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08
Note 2 -
Suitable for Field and Factory wiring.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.