ULiQfor Surge Protective Devices

Surge Protective DevicesE319777
Guide Information
DEHN SE
Hans-Dehn-Strasse 1, Neumarkt 92318 DE
Cat No(s): 952 307
DEHNguard M
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)

Notes
4CA690/400AC3Yn/a-4085L-L-47401500n/a10n/a2
L-G-3460750-
4CA600AC3Dn/a-4085L-L-47401500n/a10n/a2
L-G-3460750-
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08
Note 2 - Suitable for Field and Factory wiring.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2009-11-19© 2025 UL Solutions
Last Revised:2021-09-29