UL
iQ
for Surge Protective Devices
Surge Protective Devices
E326289
Guide Information
Citel America Inc
10108 USA Today Way, Miramar FL 33025
Cat No(s): DS240-120/G
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)
Notes
4CA (5)
240/120
AC
1S
n/a
-40
60
L-N
-
1460
150
n/a
20
n/a
1
L-G
-
1890
150
n/a
N-G
-
1340
255
n/a
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08 and CSA C22.2 No. 269.5-17, 2017-09
Note 1 -
Suitable for Factory wiring only.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2012-05-12
© 2024 UL Solutions
Last Revised:
2023-02-15