UL
iQ
for Surge Protective Devices
Surge Protective Devices
E326289
Guide Information
Citel America Inc
10108 USA Today Way, Miramar FL 33025
Cat No(s): DS230S-48DC
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)
Notes
4CA (5)
48
DC
-
n/a
-40
85
DC+-DC-
-
710
65
n/a
10
n/a
1
DC+-G
-
540
65
n/a
DC--G
-
560
65
n/a
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15 and CSA C22.2 No. 269.5-17, 2017-09
Note 1 -
Suitable for Factory wiring only.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2012-04-07
© 2024 UL Solutions
Last Revised: