Surge Protective Devices
E325047
Guide Information
ERICO INTERNATIONAL CORPORATION
34600 SOLON RD, SOLON OH 44139-2631
Cat No(s): TDS1301T%150
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)
Notes
4CA
240/120
AC
1S
n/a
-35
85
L-N
-
880
170
n/a
3
n/a
1,4
L-G
-
570
170
n/a
N-G
-
570
170
n/a
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08
% -
Blank or "R"
Note 1 -
Suitable for Factory wiring only.
Note 4 -
Series External Overcurrent Protection required, see Electrical Ratings in the Recognition report.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.