UL
iQ
for Surge Protective Devices
Surge Protective Devices
E320116
Guide Information
LITTELFUSE INC
8755 W HIGGINS RD STE 500, CHICAGO IL 60631
Cat No(s): LSP10GIHP277S (h)
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)
Notes
4CA (5)
120
AC
1
5
-40
75
L-N
-
810
320
n/a
10
n/a
2,4
L-G
-
1560
320
n/a
N-G
-
1570
320
n/a
4CA (5)
127
AC
1
5
-40
75
L-N
-
810
320
n/a
10
n/a
2,4
L-G
-
1560
320
n/a
N-G
-
1570
320
n/a
4CA (5)
240
AC
1
5
-40
75
L-N
-
810
320
n/a
10
n/a
2,4
L-G
-
1560
320
n/a
N-G
-
1570
320
n/a
4CA (5)
277
AC
1
5
-40
75
L-N
-
810
320
n/a
10
n/a
2,4
L-G
-
1560
320
n/a
N-G
-
1570
320
n/a
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08 and CSA C22.2 No. 269.5-17, 2017-09
(h) -
May be followed by additional suffixes
Note -
Each model may be suffixed by X, where X may be blank, A thru Z or from 0 thru 9.
Note 2 -
Suitable for Field and Factory wiring.
Note 4 -
Series External Overcurrent Protection required, see Electrical Ratings in the Recognition report.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2015-12-28
© 2024 UL Solutions
Last Revised:
2023-05-25