ULiQfor Surge Protective Devices

Surge Protective DevicesE326289
Guide Information
Citel America Inc
10108 USA Today Way, Miramar FL 33025
Model(s): DS74US-600D
Open-Type SPD
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1600AC3Dn/a-4085L-L250084020200
L-G2500840
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15 and CSA C22.2 No. 269.1-17, 2017-02
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2016-06-19© 2024 UL Solutions
Last Revised:2023-10-06