UL
iQ
for Surge Protective Devices
Surge Protective Devices
E321351
Guide Information
Schneider Electric USA, Inc.
Schneider Electric, SURGE PROTECTION BUSINESS, 1751 S 4800 W, Salt Lake City UT 84104
Model(s): S50A1500VDC(d), SPDC15
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1
1500
DC PV
-
n/a
-35
85
DC+-DC-
3000
1500
20
100
DC+-G
3000
1500
DC--G
3000
1500
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15
(d) -
May be followed by PV, followed by blank, G, R or M, may be followed by an additional number or letter.
Note -
Unless specified otherwise, all models may be followed by additional suffixes.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2015-09-16
© 2026 UL Solutions
Last Revised:
2023-09-28